Data-center liquid cooling coolants

Updated 22 October 2026 · Independent, sourced reference

Quick answer

Most direct-to-chip liquid cooling for AI servers uses a water/propylene-glycol mix, typically PG25 (25% PG with inhibitors), in a sealed secondary loop driven by a CDU. Immersion cooling instead submerges hardware in a dielectric fluid (single-phase or two-phase). Fluid choice depends on hardware vendor approvals, qualifications such as NVIDIA DSX Ready, and the maintenance program.

Key takeaways

  • Direct-to-chip: water/glycol (often PG25) in a sealed secondary loop.
  • Immersion: non-conductive dielectric fluids.
  • A CDU separates the technology loop from facility water.
  • Hardware and CDU vendor approval comes first.
  • Fluid maintenance (concentration, inhibitors, filtration) is ongoing.

How data-center liquid cooling loops work

A facility water loop rejects heat to chillers, dry coolers or towers. A coolant distribution unit (CDU) with a heat exchanger transfers heat from the technology cooling system (TCS), the secondary loop that runs through cold plates on GPUs and CPUs. The TCS fluid is what "data-center coolant" usually means.

Server rack cold plate on GPUcold plate on CPU CDUpump · filter · heat exchanger Facility waterto chillers / dry coolers warmcool Technology cooling loop (e.g. PG25)Facility loop
Direct-to-chip cooling: the PG25 or water-based coolant stays in a closed technology loop; the CDU passes heat to the facility water loop.

Coolant types used

TypeWhereExamples (see profiles)
PG25 (water + 25% propylene glycol + inhibitors)Direct-to-chip secondary loopsBASF, Shell, Castrol, Dow, Valvoline, Dynalene, PFX
Other glycol/water OAT fluidsDirect-to-chipArteco ZITREC EC (MPG/MEG/water-based)
Single-phase dielectricImmersion tanksShell, Engineered Fluids, Submer, Valvoline DE1
Two-phase dielectricTwo-phase immersionChemours Opteon 2P50 (developmental)

Qualifications and standards

Public qualifications include NVIDIA DSX Ready coolant qualifications, the Open Compute Project (OCP) PG25 guideline and marketplace listings, and immersion certification programs such as Intel's. See the qualified coolants list. A qualification doesn't replace your hardware vendor's approval.

Choosing a fluid: checklist

  • On your cold-plate and CDU vendors' approved lists?
  • Ready-to-use (PG25) vs concentrate?
  • Inhibitor chemistry and wetted-material compatibility
  • Maintenance limits and sampling program
  • Supply and service in your region

Explore

In-row vs in-rack CDUs

CDUs come in different forms. In-rack units sit inside a single rack and serve its cold plates. In-row or floor-standing units serve several racks through a manifold network. Liquid-to-air units reject heat into the room air (useful for retrofits without facility water), and liquid-to-liquid units transfer heat to facility water. The fluid choice is usually tied to the CDU vendor's and server vendor's approvals.

Commissioning a new loop

  1. Clean and flush the new pipework per the CDU and fluid supplier guidance.
  2. Fill with the approved, pre-diluted fluid, avoiding contamination.
  3. Vent the air and verify flow and pressure.
  4. Take baseline samples (concentration, pH, conductivity, appearance).
  5. Set up the monitoring and sampling schedule.

ASHRAE W classes for facility water

ASHRAE renamed its liquid-cooling water classes so the upper temperature limit is part of the name. Warmer classes allow more hours of chiller-free cooling, and with W45 and W+ waste heat can be reused, for example in district heating, but they need IT equipment and CDUs designed for warmer inlet fluid.

ASHRAE classFacility water supply temperature (upper limit)Typical heat rejection (per ASHRAE)
W1717 °CChiller / cooling tower
W2727 °CCooling tower, water-side economizer
W3232 °CCooling tower
W4040 °CCooling tower or dry cooler
W4545 °CCooling tower or dry cooler; district heating possible
W+>45 °CDistrict heating

All classes carry a 2 °C minimum. W classes describe the facility water supply (FWS), not the fluid temperature at the IT equipment, which is typically several degrees warmer after the CDU approach.

Comparing data-center fluids?

Open comparator →

Standards and guidance you should know

DocumentPublisherWhat it covers
Liquid Cooling Guidelines for Datacom Equipment CentersASHRAE TC9.9FWS and TCS design, water quality (chapters 5 and 6)
Water-Cooled Servers white paperASHRAE TC9.9Common designs, components, water quality
TC9.9 Technical BulletinsASHRAE TC9.9TCS cleaning, commissioning and monitoring
PG25 Guidelines Rev 2.0Open Compute ProjectPG25 in the TCS: materials, cleaning, filtration, monitoring
PG25 Base Specification v1.0.0Open Compute ProjectBaseline production requirements for PG25 fluid suppliers

For the suppliers making these fluids, see the supplier directory.

ASHRAE facility water temperature classes

ASHRAE renamed its classes to include the upper supply-temperature limit. Warmer classes extend free cooling and enable heat reuse, provided the IT hardware supports the resulting inlet temperatures.

ASHRAE classFacility water supply temperature (upper limit)Typical heat rejection (per ASHRAE)
W1717 °CChiller / cooling tower
W2727 °CCooling tower, water-side economizer
W3232 °CCooling tower
W4040 °CCooling tower or dry cooler
W4545 °CCooling tower or dry cooler; district heating possible
W+>45 °CDistrict heating

All classes carry a 2 °C minimum. W classes describe the facility water supply (FWS), not the fluid temperature at the IT equipment, which is typically several degrees warmer after the CDU approach.

Where each loop's water-quality rules live

Facility and IT-side loops have different water-quality guidance. The table and explanation are on our CDU coolant maintenance page, alongside the monitoring parameters ASHRAE bulletins list.

Who owns what in a liquid-cooled hall

ElementTypical owner
Facility water plant (chillers, towers, dry coolers)Facilities / building owner
CDU and secondary pipingCDU vendor, integrator, or operator
Cold plates and server manifoldsIT hardware vendor
TCS fluidSpecified with the hardware/CDU vendors; supplied by the fluid maker
Monitoring and samplingOperator, often with the fluid supplier

Further reading

More questions answered

Is liquid cooling only for AI?

It's widely used for high-density compute, including AI and HPC.

Reader questions

Do liquid-cooled racks still need air cooling?

Often for remaining components, depending on design.

Key point to remember

Start with hardware approvals, then fluid and monitoring.

In practice

In practice, document everything.

Frequently asked questions

What coolant is used in data centers?

Direct-to-chip systems typically use PG25 water/glycol. Immersion uses dielectric fluids.

What is a CDU?

A coolant distribution unit that pumps the secondary loop and exchanges heat with facility water.

Sources

  1. Arteco: offices
  2. BASF news release, Oct 2026
  3. Data Centre Magazine: NVIDIA qualifies Shell DLC fluid
  4. Castrol newsroom
  5. Valvoline Global: Beyond launch
  6. Dow: DOWFROST LC 25 product page
  7. ASHRAE TC9.9 white paper: Water-Cooled Servers: Common Designs, Components, and Processes
  8. ASHRAE TC9.9 white paper: Emergence and Expansion of Liquid Cooling in Mainstream Data Centers
  9. OCP: Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks (Rev 2.0, Sep 2026)
  10. OCP: Base Specification for Single-Phase PG25 fluids v1.0.0