Facility water vs technology cooling system

Updated 7 November 2026 · Independent, sourced reference

Quick answer

Liquid-cooled data centers run two loops. The facility water system (FWS) carries heat to chillers, dry coolers or cooling towers. The technology cooling system (TCS) is the clean, closed loop that reaches the cold plates. A CDU links them through a heat exchanger. ASHRAE classifies facility water by maximum supply temperature (W17, W27, W32, W40, W45, W+).

Key takeaways

  • The TCS coolant (often PG25) never mixes with facility water.
  • ASHRAE W classes name the highest facility water supply temperature equipment must tolerate.
  • The CDU approach means the TCS runs some degrees warmer than the FWS supply.
On this page

Request sourcing help for your liquid-cooling project

One short form: fluid, volume, region and your work email. Free for buyers — every request is reviewed by a person.

Free for buyers Manual human review

  1. 1 Your requirements
  2. 2 Contact details

Step 1 of 2 · What do you need?

Step 2 of 2 · Where can we reach you?

We review requests manually. A supplier introduction or response time isn’t guaranteed. Suppliers may pay for introductions; our guidance stays independent.

  • Shared with suppliers only with your consent
  • Never sold or used for newsletters

Your details are used to review and source your request, retained for up to 12 months, and deleted on request to [email protected]. Privacy & terms.

The two loops

Facility water system (FWS)Technology cooling system (TCS)
WhereBuilding plant to the CDUCDU to the cold plates in the racks
FluidTreated water or glycol, building-gradeTightly specified coolant, e.g. PG25 or treated water
CleanlinessBuilding water treatment standardsFine filtration, strict chemistry and microbiology control
Rejects heat toChillers, dry coolers, cooling towersThe CDU heat exchanger

ASHRAE W classes

ASHRAE TC 9.9 introduced liquid cooling classes in 2011. The fifth edition of its Thermal Guidelines renamed them by the maximum facility water supply temperature: W17, W27, W32, W40, W45 and W+ (above 45 °C). Warmer classes allow more free cooling and heat reuse but leave less margin for the chips.

Because the CDU heat exchanger needs a temperature difference (the approach), the TCS supply is warmer than the FWS supply by several degrees. Check that the hardware is rated for the resulting coolant temperature, not only for the facility water class.

Coolant on each side

  • TCS: follow the server and CDU makers’ fluid specification, for example OCP PG25 guidance. See what is PG25.
  • FWS: building water treatment, sometimes glycol where freezing is possible in dry coolers.

Related: what is a CDU · CDU coolant maintenance.

Free: liquid-cooling fluid RFQ checklist

Two pages: what to specify, documents to demand, and a grid to compare three supplier quotes.

Get the checklist →

Frequently asked questions

What is the difference between FWS and TCS?

FWS is the facility water loop to the building plant; TCS is the closed coolant loop from the CDU to the IT equipment.

What are ASHRAE W classes?

Facility water classes named by maximum supply temperature: W17, W27, W32, W40, W45 and W+ (fifth edition).

How we source this page

  • Facts come from manufacturer pages, datasheets, owner's manuals and standards bodies, linked under Sources.
  • We do not test products, and no brand pays to be listed or ranked. Advertising and affiliate links are labelled and never change the data.
  • Anything we could not find is marked "not published" rather than guessed. Spotted an error? Tell us.

Sources

  1. Upsite: ASHRAE fifth edition Thermal Guidelines, liquid cooling chapter updates
  2. ASHRAE TC9.9 white paper: Water-cooled servers
  3. Vertiv: Understanding CDUs for liquid cooling
Need this fluid? Free supplier quotesGet quotes