Direct-to-chip vs immersion cooling

Updated 22 October 2026 · Independent, sourced reference

Quick answer

Direct-to-chip vs immersion cooling, in brief: Direct-to-chip pumps a water/glycol coolant (often PG25) through cold plates on the hottest chips, while other components remain air-cooled. Immersion submerges whole servers in a dielectric fluid, either single-phase (it stays liquid) or two-phase (it boils and condenses). Direct-to-chip fits existing rack designs more easily. Immersion captures nearly all heat but changes servicing and hardware choices.

Key takeaways

  • Direct-to-chip: conductive coolant, so it must stay inside the loop.
  • Immersion: non-conductive fluid, in contact with the hardware.
  • Two-phase immersion uses engineered fluids that boil at low temperatures.
  • Hardware warranty and serviceability decide most projects.
  • Many AI deployments today use direct-to-chip.

How each works

Direct-to-chipSingle-phase immersionTwo-phase immersion
FluidWater/glycol (PG25)Dielectric oil/syntheticLow-boiling dielectric
ContactCold plates onlyWhole serverWhole server
Heat removalChips (rest air-cooled)Nearly allNearly all
ExamplesShell DLC S3, DOWFROST LCSubmer SmartCoolant, ElectroCoolChemours Opteon 2P50 (developmental)
Server rack cold plate on GPUcold plate on CPU CDUpump · filter · heat exchanger Facility waterto chillers / dry coolers warmcool Technology cooling loop (e.g. PG25)Facility loop
Direct-to-chip cooling: the PG25 or water-based coolant stays in a closed technology loop; the CDU passes heat to the facility water loop.

Pros and cons

ProsCons
Direct-to-chipFits standard racks; mature supply of PG25 fluidsLeak risk; still needs some air cooling
ImmersionVery high heat capture; quietTank form factor; servicing and hardware compatibility

Decision checklist

  • Rack density and future roadmap
  • Hardware vendor support and warranty
  • Facility water temperature
  • Serviceability and staff training
  • Fluid supply and lifecycle

Single-phase vs two-phase immersion

In single-phase immersion, servers sit in a tank of dielectric fluid that stays liquid. It's pumped through a heat exchanger to remove heat. In two-phase immersion, the fluid has a low boiling point. It boils at the hot components, the vapour condenses on a cooled coil above, and it drips back. Two-phase can move very high heat flux, but its fluids are specialized. Some historical two-phase fluid families have faced regulatory and supply changes, which is one reason newer HFO-based options are being developed (see the Chemours profile).

Hybrid approaches

Many deployments combine methods: cold plates on GPUs and CPUs with rear-door heat exchangers or air for the remaining components, or immersion for some racks and direct-to-chip for others. The right mix depends on the hardware roadmap and the facility.

Where each fits in the ASHRAE loop model

Direct-to-chip systems map directly onto ASHRAE's FWS/TCS model: the cold plates sit on the TCS, a CDU transfers heat to facility water, and the TCS fluid must meet strict quality requirements (see the table on the hub page). Immersion systems also use a heat exchanger to move heat from the dielectric fluid to facility water, but the fluid itself surrounds the electronics, so its electrical properties, material compatibility with cables, labels and thermal pastes, and long-term stability become the key questions.

Fluid questions for each approach

QuestionDirect-to-chip (PG25)Immersion (dielectric)
Main reference documentsASHRAE TC9.9 TCS guidance; OCP PG25 guidelines and base specVendor and certification programs (e.g. Intel immersion certification cited by Shell)
Key fluid checkspH, conductivity, glycol %, inhibitor reserve, microbesSupplier-specified properties: not published here
Leak consequenceConductive fluid near electronicsFluid is already in contact, by design
Top-upSame pre-diluted fluidSame fluid, per the supplier
ServiceabilityStandard rack access with quick-disconnectsServers lifted from tanks

Facility water temperature and heat reuse

Both approaches can work with warm facility water. ASHRAE's renamed W classes run from W17 to W45 and W+ (above 45 °C). Warmer water increases free-cooling hours and opens heat-reuse options, but the IT equipment's thermal requirements depend on the fluid temperature at its inlet, which is typically higher than the facility supply after the CDU approach. Confirm the supported inlet temperatures with your hardware vendor.

ASHRAE classFacility water supply temperature (upper limit)Typical heat rejection (per ASHRAE)
W1717 °CChiller / cooling tower
W2727 °CCooling tower, water-side economizer
W3232 °CCooling tower
W4040 °CCooling tower or dry cooler
W4545 °CCooling tower or dry cooler; district heating possible
W+>45 °CDistrict heating

All classes carry a 2 °C minimum. W classes describe the facility water supply (FWS), not the fluid temperature at the IT equipment, which is typically several degrees warmer after the CDU approach.

How to run a pilot

  1. Pick a representative workload and rack density.
  2. Agree on approved fluids and materials with the hardware vendor.
  3. Instrument power, temperatures, flow and fluid chemistry.
  4. Run long enough to see fluid trends, not just thermal results.
  5. Document the service procedures (swap, drain, refill) and time them.

Common misconceptions

  • "Immersion fluid never needs maintenance." Suppliers specify monitoring and filtration. Follow their program.
  • "Direct-to-chip removes all heat." Remaining components are usually still air-cooled.
  • "Any PG25 will do." Hardware approvals name specific products.

See who makes data-center and car coolants

Browse suppliers →

Bottom line

Choose by hardware support first, then facility constraints, then fluid program.

Operations: what changes for staff

TaskDirect-to-chipImmersion
Server swapDisconnect quick-disconnects; standard rack workLift the server from the tank; drip and clean
Fluid checksSample the TCS loopSample tank fluid per supplier
Spill responseGlycol-water cleanupDielectric fluid cleanup per SDS
TrainingFamiliar to HVAC/IT teamsNew procedures for most teams

Heat reuse potential

Both approaches can return warm fluid to the facility loop. Higher return temperatures improve the case for reusing the heat, for example in district heating, which ASHRAE associates with its warmest W classes.

Decision summary

If…Lean toward
Standard racks, cold-plate servers availableDirect-to-chip
Very high density, tank-ready hardwareImmersion
Mixed estateHybrid approach

More questions answered

Can I retrofit direct-to-chip into existing racks?

Often, with liquid-ready servers and a CDU, but check the hardware and facility constraints.

Reader questions

Is immersion noisier?

Immersion removes most server fans, which typically reduces noise.

Key point to remember

Pilot before committing at scale.

In practice

In practice, involve facilities, IT and fluid suppliers from day one.

Next step

Shortlist fluids in the comparator for your chosen approach.

One more tip

Ask vendors for reference sites.

Frequently asked questions

Is immersion cooling better than direct-to-chip?

Neither is universally better. It depends on density, hardware support and operations.

What fluid is used in immersion cooling?

Dielectric fluids, synthetic or hydrocarbon (single-phase), or engineered low-boiling fluids (two-phase).

Sources

  1. Intel: Shell customer story
  2. Opteon 2P50 product page
  3. Engineered Fluids: ElectroCool
  4. Submer: about us
  5. ASHRAE TC9.9 white paper: Water-Cooled Servers: Common Designs, Components, and Processes
  6. ASHRAE TC9.9 white paper: Emergence and Expansion of Liquid Cooling in Mainstream Data Centers
  7. OCP: Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks (Rev 2.0, Sep 2026)